Detection principle | Measurement of heat by means of a thermistor. |
Supply Wiring | Two wire supply, polarity insensitive |
Supply voltage | 8.5 V dc to 33 V dc |
Maximum polarity reversa | 200 ms |
Power up time | < 20 seconds |
Minimum ‘detector active’ voltage | 6 V |
Power-up surge current at 24 V | 95 µA |
Average quiescent current at 24 V | 95 µA |
Alarm current | 12 V 20 mA 24 V 40 mA |
Alarm load | 600 Ω |
Holding voltage | 5 V - 33 V |
Minimum holding current | 8 mA |
Minimum voltage to light alarm LED | 5 V |
Alarm reset voltage | < 1 V |
Alarm reset time | One second |
Alarm indicator | Integral indicator with 360º visibility |
Remote output LED (-) characteristic | 1.2 kΩ connected to negative supply |
Operating and storage temperature | -40ºC to +70ºC |
Humidity (no condensation or icing) | 0% to 98% RH |
Effect of atmospheric pressure on optical sensor | None |
Effect of wind speed | None |
Designed to IP Rating | IP23D |
Standards & approvals | EN54-5, EN54-7, MED, LR, DNV-GL, BV, ABS, CCS, KRS and CRS |
Dimensions | 97 mm diameter x 36 mm height 100 mm diameter x 51 mm height in base |
Weight | 70 g detector 130 g detector with base |
Materials | Housing: White flame-retardant polycarbonate |
Terminals: | Nickel plated stainless steel |